Requiring only 2RU (87.6mm) of rack height, the Compact DC Plant is the modular, flexible solution for a wide range of applications.
48V, Scalable from 5 amps to 250 amps
12V and 24V, Scalable from 20 amps to 300 amps
Flexible AC Input, DC Output, and Battery Interfaces
Advanced Digital Control and Communication
OUTPUT SPECIFICATIONS
-
-
-
48V: 5A, 10A, 20A, 25A, 30A, 40A, 50
NOISE
20mV RMS, 10 Hz -20 MHz bandwidth
+/- 1% over line, load, and temperature
Universal, may be configured for positive or negative grounding
AC RANGE
POWER FACTOR AND THD
|
OPERATIONAL AND ENVIRONMENTAL
-
48V: 92% typical
-
12V/24V: 90% typical
|
|
AC WIRING OPTIONS
Single, dual, or individual AC feeds
DC DISTRIBUTION OPTIONS
-
Options for bulk termination, circuit breakers, or fuses
-
Options for LVD contactor for load or battery
|
OTHER OPTIONS
CONTROL AND COMMUNICATIONS
STANDARD FEATURES
-
16 Character front panel display
-
Battery float control with temperature compensation
-
Battery boost / equalize control
-
Three external and one internal temperature probes
-
Battery recharge and system current limit
-
Six programmable form-C relays
-
Up to four external, programmable alarm inputs
|
OTHER OPTIONS
-
10/100 LAN with HTTP, SNMP, Telnet
-
MODEM interface with VT100
|
MECHANICAL
DIMENSIONS
-
Height: 87.6mm (3.45") (2RU)
-
Width: Fits EIA standard 482.6mm (19") or 584.2mm (23") racks
-
Depth: 304.8mm (12") (front access with front wire)
-
Depth: 381.0mm (15") (front access with rear wire)
|
WEIGHT
AGENCY CERTIFICATIONS
-
TELCORDIA: NEBS Level 3, NRTL Certified
-
UL: Canada/US UL60950/UL1801
-
VDE: EN60950
-
EMI/EMC: CISPR Class B conducted and radiated 10V/M radiated susceptibility
- CE mark meets 73/23/EEC and 93/68/EEC directives
|
|